Schneider Miniature Circuit Breaker, Easy9, 1P, 20 A, C curve, 3 kA
Miniature Circuit Breaker
Specifications
Main
| Range |
Easy9 |
| Device application |
Distribution |
| Product or component type |
Miniature circuit-breaker |
| Device short name |
Easy9 MCB |
| Poles |
1P |
| Number of protected poles |
1 |
| [In] rated current |
20 A |
| Network type |
AC |
| Trip unit technology |
Thermal-magnetic |
| Curve code |
C |
| Breaking capacity |
3 kA Icu at 230 V AC 50/60 Hz conforming to SANS 60947-2 |
| Utilisation category |
Category A |
| Suitability for isolation |
Yes conforming to SANS 60947-2 |
Complementary
| Network frequency |
50/60 Hz |
| [Ue] rated operational voltage |
230 V AC 50/60 Hz |
| Magnetic tripping limit |
8.5 x In +/- 20 % |
| [Ics] rated service breaking capacity |
3 kA 100 % x Icu at 230 V AC 50/60 Hz conforming to SANS 60947-2 |
| Limitation class |
3 conforming to SANS 60947-2 |
| [Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to SANS 60947-2 |
| [Uimp] rated impulse withstand voltage |
4 kV conforming to SANS 60947-2 |
| Contact position indicator |
Yes |
| control type |
Toggle |
| Local signalling |
Without |
| Mounting mode |
Clip-on |
| Mounting support |
DIN rail |
| 9 mm pitches |
2 |
| Height |
81 mm |
| Width |
18 mm |
| Depth |
66.5 mm |
| Net weight |
0.105 kg |
| Colour |
Grey (RAL 7035) |
| Mechanical durability |
10000 cycles |
| Electrical durability |
4000 cycles |
| Connections - terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid Tunnel type terminal (top or bottom) 1…25 mm² flexible |
| Tightening torque |
2 N.m top or bottom |
Environment
| Standards |
SANS 60947-2 |
| Product certifications |
CE |
| IP degree of protection |
IP20 conforming to IEC 60529 |
| Pollution degree |
2 |
| Relative humidity |
95 % at -5…60 °C |
| Ambient air temperature for operation |
-5…60 °C |
| Ambient air temperature for storage |
-40…85 °C |