RAD-868-IFS Radioline Electronic Module
RAD-868-IFS Radioline Electronic Module
Specifications
| Insulation characteristics |
| Overvoltage category |
II |
| Degree of pollution |
2 |
Electrical properties
| Rated insulation voltage |
60 V (In accordance with EN/IEC 60079-7) |
| Transient surge protection |
Yes |
| System limits |
| Designation |
Wireless module |
| Number of supported devices |
≤ 99 (per wireless network) |
| Number of possible extension modules |
≤ 32 (per wireless module) |
| System limits |
| Designation |
Wireless network |
| I/O data mode |
≤ 99 (I/O extension modules per wireless network, serial interfaces deactivated) |
| Serial data mode |
0 (no I/O extension modules can be used) |
| PLC/Modbus RTU mode |
≤ 99 (I/O extension modules per wireless network, access to extension modules via Modbus RTU protocol) |
| Supply |
| Supply voltage |
24 V DC |
| Supply voltage range |
19.2 V DC ... 30.5 V DC |
| Max. current consumption |
≤ 65 mA (at 24 V DC, at 25 °C, stand-alone) |
| ≤ 6 A (at 24 V DC, with DIN rail connector at full capacity) |
Output data
| Digital |
| Output name |
RF link relay output |
| Number of outputs |
1 |
| Contact type |
Changeover contact |
| Contact material |
PdRu, gold-plated |
| Maximum switching voltage |
30 V AC |
| 60 V DC |
| Max. switching current |
500 mA |
| Electrical service life |
5x 105 switching cycles with 0.5 A at 30 V DC |
| Analog |
| Output name |
RSSI voltage output |
| Number of outputs |
1 |
| Voltage output signal |
0 V ... 3 V |
Connection data
| Connection method |
Screw connection |
| Stripping length |
7 mm |
| Conductor cross section solid min. |
0.2 mm² |
| Conductor cross section solid max. |
2.5 mm² |
| Conductor cross section flexible min. |
0.2 mm² |
| Conductor cross section flexible max. |
2.5 mm² |
| Conductor cross section AWG min. |
24 |
| Conductor cross section AWG max. |
14 |
Interfaces
| Wireless |
| Range |
± 20 km (The range may be considerably above or below that stated, and depends on the environment, antenna technology, and the product used) |
| Serial: RS-232 |
| Data rate |
300 bps / 600 bps / 1.2 kbps / 2.4 kbps / 4.8 kbps / 9.6 kbps / 19.2 kbps / 38.4 kbps / 57.6 kbps / 93.75 kbps / 115.2 kbps |
| Connection method |
COMBICON plug-in screw terminal block |
| Connection technology |
3-conductor |
| Transmission length |
≤ 15 m |
| Serial: RS-485 |
| Data rate |
300 bps / 600 bps / 1.2 kbps / 2.4 kbps / 4.8 kbps / 9.6 kbps / 19.2 kbps / 38.4 kbps / 57.6 kbps / 93.75 kbps / 115.2 kbps |
| Connection method |
COMBICON plug-in screw terminal block |
| Connection technology |
2-conductor |
| Transmission length |
≤ 1200 m |
| Termination resistor |
390 Ω (switchable via DIP switches) |
| 150 Ω (switchable via DIP switches) |
| 390 Ω (switchable via DIP switches) |
| Serial: Configuration interface |
| Connection method |
S-PORT (socket) |
| Wireless |
| Interface description |
Trusted Wireless |
| Direction |
Bi-directional |
| Frequency |
868 MHz |
| Frequency range |
869.4 MHz ... 869.65 MHz |
| Channel distance |
30 kHz (Depending on the network structure and the data transmission rate) |
| Number of channel groups |
14 |
| Transmit capacity, minimum |
16 dBm |
| Transmit capacity, maximum |
≤ 27 dBm (500 mW, default setting, adjustable) |
Additional Information
| Device |
Electronic Module |
| Type |
RAD-868-IFS | Radioline |